The W Series Vertical is a high static, ducted vertical cased fan coil with bottom return. Primarily used in vertical floor-mounted or hideaway applications, the W Series is furred into partition walls or hidden in closets, utility rooms and other concealed locations with a ducted discharge. A removable front access panel facilitates easy servicing. A one-inch discharge duct flange is standard on the top panel of each unit.

The V Series Vertical Front Return is a high static, ducted vertical fan coil for installation in a closet-type enclosure. The front panel is removable for easy service access to the slide-out blower assembly, with quick-connect plug. V Series with return-air grille option allows unit to be furred-in. Grille mounts to drywall for easy access without the expense of a closet door.


Unit Type
Unit Size
Rated CFM
GPM
P.D. - FT.
H2O
Cooling Capacity
Total Cooling BTUH
Sensible Cooling BTUH
Power Input Watts
V
400
530
3.2
2.1
15,930
11,690
175
V
600
730
3.8
1.0
20,700
16,900
260
V
800
960
5.5
2.1
29,400
23,000
360
V
1000
1,060
6.2
3.0
34,000
26,400
383
V
1200
1,300
7.4
4.8
43,000
32,800
540
V
1500
1,580
10.6
6.0
56,000
41,000
533**
V
1800
1,840
12.5
9.2
67,000
49,000
654**
V
2200
2,010
14.0
12.4
75,000
54,300
768**

Notes: Based on 80° DB and 67° WB EAT, 45° F EWT, 10° F temperature rise, high fan speed. Motor voltage 115/1/60 power source.
Air flow under dry coil conditions. Water pressure drops shown in feet of water. ** Data shown for two (2) motors.